    Please use this identifier to cite or link to this item: http://ir.lib.cyut.edu.tw:8080/handle/310901800/12820


    Title: Response of Piping System with Semi-active Magnetorheological Damper under Tri-directional Seismic Excitation
    Authors: Praveen Kumar;R.S. Jangid;G.R. Reddy
    Contributors: 理工學院;Department of Civil Engineering,Indian Institute of Technology Bombay, Powai, Mumbai, India
    Keywords: Seismic;earthquakes;passive control;active control;semi-active control;control algorithms;MR dampers
    Date: 2012-06
    Issue Date: 2012-08-07 13:59:24 (UTC+8)
    Publisher: 朝陽科技大學理工學院
    Abstract: Seismic loads on piping system due to earthquakes can cause excessive vibrations, which can lead to serious instability resulting in damage or complete failure of piping system.Vibrations in the piping system can be reduced using passive control, active control, semiactive control and hybrid control. In this paper, semi-active magnetorheological (MR) dampers have been studied to mitigate seismic response and vibration control in piping system used in the process industries, fossil and fissile fuel power plant. The performance of MR dampers using various control algorithms is explored. A study is also conducted on the performance of control due to variation in the command voltage of MR dampers. The effectiveness of the MR dampers in terms of the reduction in responses, namely, displacements, accelerations and base shear of the piping system are compared with uncontrolled and passive controlled responses. This study is carried out under four artificial earthquake motions with increasing amplitudes in all the three directions of motion. The analytical results demonstrate that the MR dampers under particular optimum parameters are very effective and practically implementable for the seismic response mitigation, vibration control and seismic requalification of piping system.
    Relation: International Journal of Applied Science and Engineering 10(2), p. 99-111
    國際應用科學與工程學刊10(2), p. 99-111
    Appears in Collections:[理工學院] 國際應用科學與工程學刊

    Files in This Item:

    File Description SizeFormat
    2.pdf6865KbAdobe PDF999View/Open


    All items in CYUTIR are protected by copyright, with all rights reserved.


    著作權政策宣告
    1.本網站之數位內容為朝陽科技大學所收錄之機構典藏,無償提供學術研究與公眾教育等公益性使用,惟仍請適度、合理使用本網站之內容,以尊重著作權人之權益。商業上之利用,則請先取得著作權人之授權。
    2.本網站之製作已盡力防止侵害著作權人之權益,如仍發現本網站之數位內容有侵害著作權人權益情事者,請權利人通知本網站維護人員(yjhung@cyut.edu.tw),維護人員將立即採取移除該數位著作等補救措施。

    DSpace Software Copyright © 2002-2004  MIT &  Hewlett-Packard  /   Enhanced by   NTU Library IR team Copyright ©   - Feedback